Specification
2x25A or 2x40A AC load current.
280 or 480V AC load voltage.
8-30V AC/DC or 90-240V AC input voltage.
LED status indicators for input voltages.
Zero-cross switching.
Applicable for three phase loads.
Built-in varistor protection.
Rail mountable.
CE marked according to European Norms.

Ambient/storage temperature |
-25... +60 C / -30... +100 C (In the environment icing and condensation should not be.) |
Overvoltage category |
II |
Altitude |
max. 1000m |
Protection |
IP20 According to EN60529 |
Order Code |
ERxA2-225Z
|
ERxA2-240Z-F
|
ERxA2-425Z
|
ERxA2-440Z-F
|
Load current, AC51/25ºC (Arms) |
2x25 |
2x40 |
2x25 |
2x40 |
Load voltage (Vrms) |
24 - 280 |
50 - 480 |
Overload current t=1s/25°C (Arms) |
85 |
150 |
70 |
110 |
Non rep.surge current/25°C (Arms) |
250 |
400 |
190 |
290 |
On-state voltage drop (Vrms) |
1,6 |
1,8 |
Leakage current (mArms) |
5 |
8 |
I²t for fusing t=10ms (A²s) |
340 |
880 |
265 |
610 |
Frequency (Hz) |
50 - 60 |
50 - 60 |
Min. operating current (mArms) |
160 |
200 |
Order Code |
ERDA2-xxxZ
|
ERAA2-xxxZ
|
Input voltage |
2 x 8 - 30Vac/dc |
2 x 90 - 240Vac |
Pick-up voltage |
> 6Vac/dc |
> 75Vac |
Drop-out voltage |
< 2Vac/dc |
< 6Vac |
Input current |
< 2 x 17mAac/2 x10mAdc |
< 2 x 8mAac |
Turn-on time |
Maximum ½ Period |
Maximum 1 Period |
Turn-off time |
Maximum ½ Period |
Maximum 1 Period |
LED indicator |
If the input voltage >6V ac/dc, LED lights up. |
If the input voltage >75V ac, LED lights up. |
Order Code |
ERxA2-x25Z
|
ERxA2-x40Z-F
|
Dimensions |
G46xY100xD117mm |
G46xY110xD117mm |
Weight |
Approx. 475 g (After packaging) |
Approx. 500 g (After packaging) |
Isolation Voltage |
2500 Vrms 1 between I/O terminals for 1 min. |
Product standard |
EN 60947-4-3 |
|
Mounting |
Rail mountable (EN60715,TH35 or G-32) |
Enclosure material |
Self extinguishing plastics.(According to EN60695-11-10 V-O) |
Fan (option) |
Thermostat-controlled,operates at 50°C.. Fan supply: 90-240Vac. |
Characteristic
|
Connection diagram
|
 |
 |
Single Phase Load Application |
Three Phase Load Application With The Two SSRs |
 |
 |