Technical data
![]() |
![]() |
![]() |
|
Type | GAC1 | GAC2 | GAC3 |
---|---|---|---|
Power supply |
3x400 V, 50 Hz | ||
Max. current load |
30 A, 40 A, 50 A | 60 A, 80 A, 100 A, 120 A, 160 A, 180 A | 250 A, 400 A |
Power supply tolerance |
-15% ÷ +10%Un | ||
Category of use | AC-51 | ||
Features | power status, full conduction status, switching function | ||
Control signals* | 0-10 VDC 4-20 mA |
||
Thyristors control |
group | ||
Receiver connection system | star or delta | ||
Surge protection | RC suppressor | ||
Cooling | air | ||
Ingress Protection |
IP00 | ||
Insulation test voltage | 2,5 kV | ||
Degree of contamination | 3 | ||
Operating temperature range |
0 ÷ 50 °C | ||
Storage temperature range |
-20 °C ÷ 60 °C | ||
Shielding | metaplex | ||
Short-circuit protection |
fast fuses | ||
Relative humidity |
up to 85% (no condensation) | ||
Altitude | up to 1000 m | ||
Rectangle of fixing holes | 155 x 175 mm |
155 x 175 mm (GAC2 60 i 80); |
280 x 410 mm |
Dimensions (L x W x H) | 200 x 185 x 255 mm | 240 x 185 x 255 mm (DAC 60 i 80); 340 x 175 x 255 mm (other) |
340 x 380 x 260 mm |
Weight | 5,5 kg | 6-9,5 kg | 28 kg |
Attention:
*Please specify the type of control signal in your order.
Máte zájem o tento produkt? Potřebujete další informace nebo individuální ceny?
musíš být přihlášen
Use:
Power control of furnaces with resistance heaters, high-power thermal fans, air conditioners with electric heating, paint dryers.
Features:
Long service life, resistance to power line surges, surge-free on/off switching of loads, quiet operation, compliance with PN-EN 60947-4-3.
Technical data
![]() |
![]() |
![]() |
|
Type | GAC1 | GAC2 | GAC3 |
---|---|---|---|
Power supply |
3x400 V, 50 Hz | ||
Max. current load |
30 A, 40 A, 50 A | 60 A, 80 A, 100 A, 120 A, 160 A, 180 A | 250 A, 400 A |
Power supply tolerance |
-15% ÷ +10%Un | ||
Category of use | AC-51 | ||
Features | power status, full conduction status, switching function | ||
Control signals* | 0-10 VDC 4-20 mA |
||
Thyristors control |
group | ||
Receiver connection system | star or delta | ||
Surge protection | RC suppressor | ||
Cooling | air | ||
Ingress Protection |
IP00 | ||
Insulation test voltage | 2,5 kV | ||
Degree of contamination | 3 | ||
Operating temperature range |
0 ÷ 50 °C | ||
Storage temperature range |
-20 °C ÷ 60 °C | ||
Shielding | metaplex | ||
Short-circuit protection |
fast fuses | ||
Relative humidity |
up to 85% (no condensation) | ||
Altitude | up to 1000 m | ||
Rectangle of fixing holes | 155 x 175 mm |
155 x 175 mm (GAC2 60 i 80); |
280 x 410 mm |
Dimensions (L x W x H) | 200 x 185 x 255 mm | 240 x 185 x 255 mm (DAC 60 i 80); 340 x 175 x 255 mm (other) |
340 x 380 x 260 mm |
Weight | 5,5 kg | 6-9,5 kg | 28 kg |