Debes estar logueado
Category
Las fotos son solo para fines informativos. Ver especificaciones de producto
please use latin characters
• Type 2 (or 3) surge protectors for Led
• Very compact (low profile)
• DIN rail mounting
• Screw terminal connection
• Status indicator
• Disconnection AC end of life
• IEC 61643-11 and EN 61643-11 compliance

Characteristics
| Description | MLPC1-230L-V | |
|---|---|---|
| Network | 230-277V AC | |
| Max. Load current | IL | 5A |
| Max. AC operating voltage | UC | 320V AC |
| Nominal discharge current - 15 x 8/20 µs impulses |
In | 5kA |
| Max. discharge current -max. withstand @ 8/20 µs by pole |
Imax | 10kA |
| Withstand on Combination waveform - Class III test | Uoc | 10kV / 5kA |
| Withstand on overvoltages IEEE C62.41.1 | 10kV / 10kA | |
| Protection level CM/DM @In (8/20µs) and @ 6kV (1.2/50µs) |
Up | 1,5kV |
| Admissible short-circuit current | ISCCR | 10000A |
| Mechnical characteristics | |
|---|---|
| Thermal disconnector | internal |
| Dimensions | see diagram |
| Connection to Network | Screw terminal 2.5 mm² max. Earthing conductor 2 mm² - length 60 cm |
| Disconnection indicator | Disconnection and AC line cut-off |
| Failsafe behavior | Led green OFF and AC network cut-off |
| Remote signaling of disconnection | none |
| Mounting | Symmetrical rail 35mm (EN60715) |
| Operating temperature | -40 do +85°C |
| Protection rating | IP20 |
| Housing material | Thermoplastic UL94-V0 |
| Standards compliance | EN 61643-11 / IEC 61643-11 |
| Part number | |
|---|---|
| PN-EN 61643-11 Poland | surge arrester type 2+3 |
| EN 61643-11 Europe | Low Voltage SPD (class II [&] III test) |
| IEC 61643-21 International | - |
| Part number | 352913 |
Dimensions and diagrams


GDT: Gas Discharge Tube
V: Varistor
Ft: Thermal fuse
t°: Thermal system disconnection
¿Estás interesado en este producto? ¿Necesita información adicional o precios individuales?
Usted debe estar conectado
• Type 2 (or 3) surge protectors for Led
• Very compact (low profile)
• DIN rail mounting
• Screw terminal connection
• Status indicator
• Disconnection AC end of life
• IEC 61643-11 and EN 61643-11 compliance

Characteristics
| Description | MLPC1-230L-V | |
|---|---|---|
| Network | 230-277V AC | |
| Max. Load current | IL | 5A |
| Max. AC operating voltage | UC | 320V AC |
| Nominal discharge current - 15 x 8/20 µs impulses |
In | 5kA |
| Max. discharge current -max. withstand @ 8/20 µs by pole |
Imax | 10kA |
| Withstand on Combination waveform - Class III test | Uoc | 10kV / 5kA |
| Withstand on overvoltages IEEE C62.41.1 | 10kV / 10kA | |
| Protection level CM/DM @In (8/20µs) and @ 6kV (1.2/50µs) |
Up | 1,5kV |
| Admissible short-circuit current | ISCCR | 10000A |
| Mechnical characteristics | |
|---|---|
| Thermal disconnector | internal |
| Dimensions | see diagram |
| Connection to Network | Screw terminal 2.5 mm² max. Earthing conductor 2 mm² - length 60 cm |
| Disconnection indicator | Disconnection and AC line cut-off |
| Failsafe behavior | Led green OFF and AC network cut-off |
| Remote signaling of disconnection | none |
| Mounting | Symmetrical rail 35mm (EN60715) |
| Operating temperature | -40 do +85°C |
| Protection rating | IP20 |
| Housing material | Thermoplastic UL94-V0 |
| Standards compliance | EN 61643-11 / IEC 61643-11 |
| Part number | |
|---|---|
| PN-EN 61643-11 Poland | surge arrester type 2+3 |
| EN 61643-11 Europe | Low Voltage SPD (class II [&] III test) |
| IEC 61643-21 International | - |
| Part number | 352913 |
Dimensions and diagrams


GDT: Gas Discharge Tube
V: Varistor
Ft: Thermal fuse
t°: Thermal system disconnection