Thermisches Relais TS1000.
  • Thermisches Relais TS1000.
  • Thermisches Relais TS1000.

Fotos dienen nur zu Informationszwecken.

please use latin characters

Hersteller: ZIEHL

TS1000 Thermalrelais

The Trafosafe TS1000 is applied at transformers with forced cooling. It monitors the temperature of the transformer with 3 sensor-circuits (PTC-thermistors), controls the forced cooling depending on the load of the transformer, reports exceeding of alarm-temperature and switches off the transformer (trip) when increasing of the temperature continues. Up to 6 fans can be controlled and monitored directly with the TS1000. Contactors and motor protection switches are not necessary any more. At Pt 100-monitored transformers the TS1000 can be used to control only the fans.

Temperature-Monitoring

  • 1 PTC-circuit for controlling the cooling (1T1/1T2) = input for starting fan when using as fan-control only
  • 2 x 1 PTC-circuit for alarm 1 (2T1/2T2) and alarm 2/trip (3T1/3T2), monitored for short-circuit and interruption
  • Alarm1 (K2) in closed-circuit current mode = monitoring of function
  • Alarm 2/trip (K3) in open-circuit current mode = no signal/tripping when switching on the device
  • Test-/Reset-button for testing the function

Fan-Control and Monitoring of fan

  • direct connection of up to 6 fans 0.07...4.0 A
  • automatic exceeding of the on-time of the fans at high load of the transformer
  • Monitoring of failure fan (over-/undercurrent)
  • Self-calibration of the monitored values of the currents to the fans
  • Switching-point for current-failure adjustable ± 5-40%
  • automatic test of fans 1-30 days, disconnectable
  • Relay for reporting fan-failure
  • Clear displays with LEDs

General

  • Universal Power Supply AC/DC 24-240 V
  • compact housing for cabinet-mount, 140 mm wide, mounting heigt 55 mm
  • Attachment on 35 mm standard rail or with 3 screws M4

Senden Sie eine Anfrage

Interessieren Sie sich für dieses Produkt? Benötigen Sie zusätzliche Informationen oder individuelle Preise?

Kontaktiere uns

FRAGEN SIE NACH DEM PRODUKT close
Nachricht erfolgreich gesendet.
FRAGEN SIE NACH DEM PRODUKT close
Durchsuche

Zur Wunschliste hinzufügen

Sie müssen eingeloggt sein

The Trafosafe TS1000 is applied at transformers with forced cooling. It monitors the temperature of the transformer with 3 sensor-circuits (PTC-thermistors), controls the forced cooling depending on the load of the transformer, reports exceeding of alarm-temperature and switches off the transformer (trip) when increasing of the temperature continues. Up to 6 fans can be controlled and monitored directly with the TS1000. Contactors and motor protection switches are not necessary any more. At Pt 100-monitored transformers the TS1000 can be used to control only the fans.

Temperature-Monitoring

  • 1 PTC-circuit for controlling the cooling (1T1/1T2) = input for starting fan when using as fan-control only
  • 2 x 1 PTC-circuit for alarm 1 (2T1/2T2) and alarm 2/trip (3T1/3T2), monitored for short-circuit and interruption
  • Alarm1 (K2) in closed-circuit current mode = monitoring of function
  • Alarm 2/trip (K3) in open-circuit current mode = no signal/tripping when switching on the device
  • Test-/Reset-button for testing the function

Fan-Control and Monitoring of fan

  • direct connection of up to 6 fans 0.07...4.0 A
  • automatic exceeding of the on-time of the fans at high load of the transformer
  • Monitoring of failure fan (over-/undercurrent)
  • Self-calibration of the monitored values of the currents to the fans
  • Switching-point for current-failure adjustable ± 5-40%
  • automatic test of fans 1-30 days, disconnectable
  • Relay for reporting fan-failure
  • Clear displays with LEDs

General

  • Universal Power Supply AC/DC 24-240 V
  • compact housing for cabinet-mount, 140 mm wide, mounting heigt 55 mm
  • Attachment on 35 mm standard rail or with 3 screws M4