| Measured Quantities and Measuring Ranges | ||||||||
|---|---|---|---|---|---|---|---|---|
| Measured value | Indication range | Measuring range | L1 | L2 | L3 | ∑ | Basic error | |
| Current In | 1 A 5 A |
0,00...1,5 kA 0,00 ... 60 kA |
0,005...1,200 A~ 0,025...6,000 A~ | ♦ | ♦ | ♦ | ±0,2 % zak. | |
| Voltage L-N | 57,7 V 230 V 290 V |
0,0 ... 230,8 kV 0,0 ... 1,012 MV 0,0 ... 1,200 MV |
50...64 V~ 195...253V~ 246...300V~ |
♦ | ♦ | ♦ | ±0,2% w.m. | |
| Voltage L-L | 100 V 400 V 500 V |
0,0 ... 440 kV 0,0 ... 1,752 MV 0,0 ... 2,000 MV |
85...110 V~ 340 ... 440 V~ 425 ... 520 V~ |
♦ | ♦ | ♦ | ±0,5% w.m. | |
| Frequency | 47,0 .. 63,0 Hz | 47,0...63,0 Hz | ♦ | ♦ | ♦ | ±0,2% w.m. | ||
| Active power | -9999 MW .. 0,00 W .. 9999 MW | -1,52 kW...1,0 W...1,52 kW | ♦ | ♦ | ♦ | ♦ | ±0,5% w.m. | |
| Reactive power | -9999 Mvar .. 0,00 var ... 9999 Mvar | -1,52 kvar...1,0 var...1,52 kvar | ♦ | ♦ | ♦ | ♦ | ±0,5% zak. | |
| Apparent power | 0,00 VA .. 9999 MVA | 1,0VA...1,52 kVA | ♦ | ♦ | ♦ | ♦ | ±0,5% zak. | |
| Power factor PF | -1 .. 0.. 1 | -1 .. 0.. 1 | ♦ | ♦ | ♦ | ♦ | ±1% zak. | |
| Tangent φ | -1,2...0...1,2 | -1,2...0...1,2 | ♦ | ♦ | ♦ | ♦ | ±1% zak. | |
| Cosine φ | -1...1 | -1...1 | ♦ | ♦ | ♦ | ♦ | ±1% zak. | |
| φ | -180...180 | -180...180 | ♦ | ♦ | ♦ | ±0,5% zak. | ||
| Imported active energy | 0 .. 99 999 999,9 kWh | ♦ | ±0,5% zak. | |||||
| Imported active energy | 0 .. 99 999 999,9 kWh | ♦ | ±0,5% zak. | |||||
| Inductive reactive energy | 0 .. 99 999 999,9 kvarh | ♦ | ±0,5% zak. | |||||
| Reactive capacitive energy | 0 .. 99 999 999,9 kvarh | ♦ | ±0,5% zak. | |||||
| THD | 0 .. 100% | 0 .. 100% | ♦ | ♦ | ♦ | ±5% zak. | ||
| Outputs | |
|---|---|
| Output type | Properties |
| Relay output | • 2 relays, normally open voltageless contacts, load capacity 250 V~/0,5 A~ |
| Pulse output of active energy | • 1 OC type (NPN), passive class A acc. to EN 62053-31, supply voltage 18...27 V, current 10...27 mA |
| Digital interface | |||
|---|---|---|---|
| Interface type | Transmission protocol | Mode | Baud rate |
| RS-485 | MODBUS RTU | 8N2, 8E1, 8O1, 8N1 | 4,8; 9,6; 19,2; 38,4 kbit/s |
| External features | ||
|---|---|---|
| Readout field | LCD 3.5” screen, specialized, monochromatic with backlit | |
| Weight | < 0,3 kg | |
| Overall dimensions | 96 X 96 X 77 mm | panel cut-out::92+06 X 92+06 mm |
| Protection grade (acc. to EN 60529) | from frontal side: IP65 | from terminal side: IP20 |
| Rated operating conditions | ||
|---|---|---|
| Supply voltage /from measurement circuit of phase L3/ |
50...64 V a.c. , 195...253 V a.c., 246...300 V a.c.; 47...63 Hz |
Power consumption: - in voltage circuit L1,L2 ≤0,05 VA - in voltage circuit L3 ≤3 VA - in current circuits≤0,05 VA |
| Temperature | oambient:-20...23...55oC | storage:: -30 ...70oC |
| Relative humidity | 25...95% | inadmissible condensation |
| Operating position | any | |
| External magnetic field | 40...400 A/m | |
| hort duration overload (5 s) | voltage input: 2 Un | current input: 10 In |
| Safety and compatibility requirements | ||
|---|---|---|
| Electromagnetic compatibility | noise immunity | acc. to EN 61000-6-2 |
| noise emissions | acc. to EN 61000-6-4 | |
| Safety requirements | acc. to EN 61010-1 | |


EXAMPLE OF ORDER:
the code: ND10 - 2 2 1 00 E 1 means:
ND10- meter of network parameters of ND10 type,
2- current input 5 A,
2- input voltage 3 x 230/400 V,
1- with RS485 interface
00- standard version,
E- all descriptions and user's manual in English,
1- with extra quality inspection certificate.
Interessieren Sie sich für dieses Produkt? Benötigen Sie zusätzliche Informationen oder individuelle Preise?
Sie müssen eingeloggt sein

| Measured Quantities and Measuring Ranges | ||||||||
|---|---|---|---|---|---|---|---|---|
| Measured value | Indication range | Measuring range | L1 | L2 | L3 | ∑ | Basic error | |
| Current In | 1 A 5 A |
0,00...1,5 kA 0,00 ... 60 kA |
0,005...1,200 A~ 0,025...6,000 A~ | ♦ | ♦ | ♦ | ±0,2 % zak. | |
| Voltage L-N | 57,7 V 230 V 290 V |
0,0 ... 230,8 kV 0,0 ... 1,012 MV 0,0 ... 1,200 MV |
50...64 V~ 195...253V~ 246...300V~ |
♦ | ♦ | ♦ | ±0,2% w.m. | |
| Voltage L-L | 100 V 400 V 500 V |
0,0 ... 440 kV 0,0 ... 1,752 MV 0,0 ... 2,000 MV |
85...110 V~ 340 ... 440 V~ 425 ... 520 V~ |
♦ | ♦ | ♦ | ±0,5% w.m. | |
| Frequency | 47,0 .. 63,0 Hz | 47,0...63,0 Hz | ♦ | ♦ | ♦ | ±0,2% w.m. | ||
| Active power | -9999 MW .. 0,00 W .. 9999 MW | -1,52 kW...1,0 W...1,52 kW | ♦ | ♦ | ♦ | ♦ | ±0,5% w.m. | |
| Reactive power | -9999 Mvar .. 0,00 var ... 9999 Mvar | -1,52 kvar...1,0 var...1,52 kvar | ♦ | ♦ | ♦ | ♦ | ±0,5% zak. | |
| Apparent power | 0,00 VA .. 9999 MVA | 1,0VA...1,52 kVA | ♦ | ♦ | ♦ | ♦ | ±0,5% zak. | |
| Power factor PF | -1 .. 0.. 1 | -1 .. 0.. 1 | ♦ | ♦ | ♦ | ♦ | ±1% zak. | |
| Tangent φ | -1,2...0...1,2 | -1,2...0...1,2 | ♦ | ♦ | ♦ | ♦ | ±1% zak. | |
| Cosine φ | -1...1 | -1...1 | ♦ | ♦ | ♦ | ♦ | ±1% zak. | |
| φ | -180...180 | -180...180 | ♦ | ♦ | ♦ | ±0,5% zak. | ||
| Imported active energy | 0 .. 99 999 999,9 kWh | ♦ | ±0,5% zak. | |||||
| Imported active energy | 0 .. 99 999 999,9 kWh | ♦ | ±0,5% zak. | |||||
| Inductive reactive energy | 0 .. 99 999 999,9 kvarh | ♦ | ±0,5% zak. | |||||
| Reactive capacitive energy | 0 .. 99 999 999,9 kvarh | ♦ | ±0,5% zak. | |||||
| THD | 0 .. 100% | 0 .. 100% | ♦ | ♦ | ♦ | ±5% zak. | ||
| Outputs | |
|---|---|
| Output type | Properties |
| Relay output | • 2 relays, normally open voltageless contacts, load capacity 250 V~/0,5 A~ |
| Pulse output of active energy | • 1 OC type (NPN), passive class A acc. to EN 62053-31, supply voltage 18...27 V, current 10...27 mA |
| Digital interface | |||
|---|---|---|---|
| Interface type | Transmission protocol | Mode | Baud rate |
| RS-485 | MODBUS RTU | 8N2, 8E1, 8O1, 8N1 | 4,8; 9,6; 19,2; 38,4 kbit/s |
| External features | ||
|---|---|---|
| Readout field | LCD 3.5” screen, specialized, monochromatic with backlit | |
| Weight | < 0,3 kg | |
| Overall dimensions | 96 X 96 X 77 mm | panel cut-out::92+06 X 92+06 mm |
| Protection grade (acc. to EN 60529) | from frontal side: IP65 | from terminal side: IP20 |
| Rated operating conditions | ||
|---|---|---|
| Supply voltage /from measurement circuit of phase L3/ |
50...64 V a.c. , 195...253 V a.c., 246...300 V a.c.; 47...63 Hz |
Power consumption: - in voltage circuit L1,L2 ≤0,05 VA - in voltage circuit L3 ≤3 VA - in current circuits≤0,05 VA |
| Temperature | oambient:-20...23...55oC | storage:: -30 ...70oC |
| Relative humidity | 25...95% | inadmissible condensation |
| Operating position | any | |
| External magnetic field | 40...400 A/m | |
| hort duration overload (5 s) | voltage input: 2 Un | current input: 10 In |
| Safety and compatibility requirements | ||
|---|---|---|
| Electromagnetic compatibility | noise immunity | acc. to EN 61000-6-2 |
| noise emissions | acc. to EN 61000-6-4 | |
| Safety requirements | acc. to EN 61010-1 | |


EXAMPLE OF ORDER:
the code: ND10 - 2 2 1 00 E 1 means:
ND10- meter of network parameters of ND10 type,
2- current input 5 A,
2- input voltage 3 x 230/400 V,
1- with RS485 interface
00- standard version,
E- all descriptions and user's manual in English,
1- with extra quality inspection certificate.