BackX
-
All categories
-
-
Category
-
Semiconductors
- Diodes
- Thyristors
-
Electro-insulated Modules
- Electro-insulated Modules | VISHAY (IR)
- Electro-insulated Modules | INFINEON (EUPEC)
- Electro-insulated Modules | Semikron
- Electro-insulated Modules | POWEREX
- Electro-insulated Modules | IXYS
- Electro-insulated Modules | POSEICO
- Electro-insulated Modules | ABB
- Electro-insulated Modules | TECHSEM
- Go to the subcategory
- Bridge Rectifiers
-
Transistors
- Transistors | GeneSiC
- SiC MOSFET Modules | Mitsubishi
- SiC MOSFET Modules | STARPOWER
- Module SiC MOSFET ABB’s
- IGBT Modules | MITSUBISHI
- Transistor Modules | MITSUBISHI
- MOSFET Modules | MITSUBISHI
- Transistor Modules | ABB
- IGBT Modules | POWEREX
- IGBT Modules | INFINEON (EUPEC)
- Silicon Carbide (SiC) semiconductor elements
- Go to the subcategory
- Gate Drivers
- Power Blocks
- Go to the subcategory
-
Electrical Transducers
-
Current Transducers | LEM
- Closed-Loop Current Transducers (C/L)
- Open-Loop Current Transducers (O/L)
- Current Transducers supplied with unipolar voltage
- 'Eta' Current Transducers
- Current Transducers - LF xx10 Series
- Current Transducers - LH Series
- Current Transducer - HOYL and HOYS Series
- Current Transducers - GO–SME & GO–SMS Series
- AUTOMOTIVE current transducers
- Go to the subcategory
-
Voltage Transducers | LEM
- Voltage Transducers - LV Series
- Voltage Transducers - DVL Series
- Precision Voltage Transducers with double magnetic core - CV Series
- Voltage Transducer for Traction - DV 4200/SP4
- Voltage Transducers - DVM Series
- Voltage Transducer - DVC 1000-P
- Voltage Transducers - DVC 1000 Series
- Go to the subcategory
- Transducers for Protection, Monitoring and Control | LEM
- Split-core Transducers | LEM
- Precision Current Transducers | LEM
- Go to the subcategory
-
Current Transducers | LEM
-
Passive components (capacitors, resistors, fuses, filters)
- Resistors
-
Fuses
- Miniature Fuses for electronic circuits - ABC & AGC Series
- Tubular Fast-acting Fuses
- Time-delay Fuse Links with GL/GG & AM characteristics
- Ultrafast Fuse Links
- Fast-acting Fuses (British & American standard)
- Fast-acting Fuses (European standard)
- Traction Fuses
- High-voltage Fuse Links
- Go to the subcategory
- Capacitors
- EMI Filters
- Supercapacitors
- Power surge protection
- Go to the subcategory
-
Relays and Contactors
- Relays and Contactors - Theory
- 3-Phase AC Semiconductor Relays
- DC Semiconductor Relays
- Controllers, Control Systems and Accessories
- Soft Starters and Reversible Relays
- Electromechanical Relays
- Contactors
- Rotary Switches
-
Single-Phase AC Semiconductor Relays
- AC ONE PHASE RELAYS 1 series| D2425 | D2450
- One phase semiconductor AC relays CWA and CWD series
- One phase semiconductor AC relays CMRA and CMRD series
- One phase semiconductor AC relays - PS series
- Double and quadruple semiconductor AC relays - D24 D, TD24 Q, H12D48 D series
- One phase semiconductor relays - gn series
- Ckr series single phase solid state relays
- One phase AC semiconductor relays for DIN bus - ERDA I ERAA series
- 150A AC single phase relays
- Rail Mountable Solid State Relays With Integrated Heat Sink - ENDA, ERDA1 / ERAA1 series
- Go to the subcategory
- Single-Phase AC Semiconductor Relays for PCBs
- Interface Relays
- Go to the subcategory
- Cores and Other Inductive Components
- Heatsinks, Varistors, Thermal Protection
- Fans
- Air Conditioning, Accessories for Electrical Cabinets, Coolers
-
Batteries, Chargers, Buffer Power Supplies and Inverters
- Batteries, Chargers - Theoretical Description
- Modular Li-ion Battery Building Blocks, Custom Batteries, BMS
- Batteries
- Battery Chargers and Accessories
- Uninterruptible Power Supply and Buffer Power Supplies
- Inverters and Photovoltaic Equipments
- Energy storage
- Fuel cells
- Lithium-ion batteries
- Go to the subcategory
-
Automatics
- Limit Switches, Microswitches
- Sensors, Transducers
-
Infrared Thermometers (Pyrometers)
- IR-TE Series - Water-proof Palm-sized Radiation Thermometer
- IR-TA Series - Handheld Type Radiation Thermometer
- IR-H Series - Handheld Type Radiation Thermometer
- IR-BA Series - High-speed Compact Radiation Thermometer
- IR-FA Series - Fiber Optic Radiation Thermometer
- IR-BZ Series - Compact Infrared Thermometers
- Go to the subcategory
- Counters, Time Relays, Panel Meters
- Industrial Protection Devices
- Light and Sound Signalling
- Thermographic Camera
- LED Displays
- Control Equipments
-
Recorders
- Hybrid Recorders - AL3000 Series | CHINO
- Graphic Recorder - KR2000 Series | CHINO
- Ubiquitous Recorders - KR5000 Series | CHINO
- Palm-sized Temperature/Humidity Meters - HN-CH Series | CHINO
- Consumables for Recorders
- 71VR1 - Compact Paperless Recorder | M-SYSTEM
- Graphic Recorder - KR3000 Series | CHINO
- PC Recorders - R1M Series | M-SYSTEM
- PC Recorders - R2M Series | M-SYSTEM
- PC Recorders - RZMS Series | M-SYSTEM
- PC Recorders - RZUS Series | M-SYSTEM
- Go to the subcategory
- Drivers and Panels
- Go to the subcategory
-
Cables, Litz wires, Conduits, Flexible connections
- Wires
- Litz wires
- Cables for extreme applications
- Sleevings
-
Braids
- Flat Braids
- Round Braids
- Very Flexible Flat Braids
- Very Flexible Round Braids
- Cylindrical Cooper Braids
- Cylindrical Cooper Braids and Sleevings
- Flexible Earthing Connections
- Galvanized and Stainless Steel Cylindrical Braids
- PCV Insulated Copper Braids (temp. up to 85C)
- Flat Aluminium Braids
- Junction Set - Braids and Tubes
- Go to the subcategory
- Traction Equipment
- Cable Terminals
- Flexible Insulated Busbars
- Flexible Multilayer Busbars
- Cable Duct Systems
- Hoses
- Go to the subcategory
- View all categories
-
Semiconductors
-
-
- Suppliers
-
Applications
- CNC Machine Tools
- DC and AC Drives (Inverters)
- Energetics
- Equipment and Components for Hazardous Areas [Ex]
- Equipment for Distribution, Control and Telecommunications Cabinets
- HVAC Automation
- Induction Heating
- Industrial Automation
- Industrial Protective Devices
- Machines for Drying and Wood Processing
- Machines for Thermoforming Plastics
- Mining, Metallurgy and Foundry
- Motors and Transformers
- Power Supplies (UPS) and Rectifier Systems
- Printing
- Temperature Measurement and Regulation
- Test and Laboratory Measurements
- Tram and Railway Traction
- Welding Machines
-
SERVICE, REPAIRS
-
-
Installation of equipment
-
- Contact
- Zobacz wszystkie kategorie
Photos are for informational purposes only. View product specification
please use latin characters
Safety switch / safety door SNO 4003K
• For immediate interruption of the power supply – stop category 0
• Monitoring of emergency stop applications
• Monitoring of safety gates
• Protective measures in sections of the safety system
The device has two reset inputs Y2 (without reset monitoring) or Y3 (with reset monitoring). The relays K1 and K2 are actuated either after the reset button (on Y1-Y3) has been pressed or automatically (bridge Y1-Y2). They become self-locking through their own contacts, if there is an electrical connection between terminal A1 and the
supply voltage (emergency stop button, position switches). After this switch-on phase the enabling current paths are closed and the signaling current path is open. If the electrical connections between terminal A1 and the supply voltage are interrupted, the enabling current paths open and the signaling current path closes. The energized state (self-locking) of the two channels is indicated by a green LED K1, K2. The second green LED indicates that supply voltage has been applied. The set-up of an emergency stop facility after stop category 0 (EN 60204-1) is possible. The device corresponds to category 4 for safety-related parts of controls (EN 954-1).
Proper use
The device is available for monitoring transducers (such as emergency stop buttons or
position switches) that are components of protective equipment on machines and are
used for the purpose of protecting people, material and machines.
• The safety category according to EN 954-1 depends on the external circuitry, the
choice of control devices and their placement on the machine.
• Expansion devices or external contactors with positively driven contacts can be used
to multiply the enabling current paths.
• The device and the contacts must be protected at max. 8 A.
• The emergency stop circuit must be closed before the reset button is activated.
• For connecting magnetic switches with reed contacts or sensors with
semiconductor outputs the peak input current must be considered (see “Technical
data”).
• The devices must be installed in a control cabinet with a protection degree of at
least IP 54.
• With AC supply and single-channel circuitry the maximum cable length for the safety
circuit of the transducers must be considered (see the notes on cable lengths and
“Technical data”
Please also note the information provided by your trade association
Cable data section 1,5 mm2
capacity 150 nF/km
resistance 28 Ω/km
temperature +25 °C
Circuit Alternating current (AC) cable not laid out in parallel,max. length lr:1 km
Tap line max. length of tap line l s and max. line capacity C L depending on supply voltage U
UB 115 230 V
CL 37,5 nF 7,5 nF
lS 250m 50 m
Overview of devices / Part numbers | ||||
---|---|---|---|---|
type | Nominal voltage | Terminals | numer sztk/opak. | |
SNO 4003K | AC/DC 24 V | 50 - 60 Hz | Terminal block, rising cage termination | R1.188.0400.1 1 |
AC 115 - 120 V | 50 - 60 Hz | Terminal block, rising cage termination | R1.188.0880.1 1 | |
AC 230 V | 50 - 60 Hz | Terminal block, rising cage termination | R1.188.0890.1 1 | |
SNO 4003K-A | AC/DC 24 V | 50 - 60 Hz | Terminal block, rising cage termination | R1.188.0500.1 1 |
AC 115 - 120 V | 50 - 60 Hz | Terminal block, rising cage termination | R1.188.0900.1 1 | |
AC 230 V | 50 - 60 Hz | Terminal block, rising cage termination | R1.188.0910.1 1 |
Technical data | SNO 4003K | ||
---|---|---|---|
Function
according to EN 60204-1
|
Emergency stop relay
|
||
Function display
|
2 LEDs green
|
||
Function diagram
|
FD 221-3-1 W, FD 221-3-2 W
|
||
Power supply circuit
|
|||
Devices with rated voltage AC / DC 24 V
|
min | typ | max |
Operating voltage range
|
AC/DC 20,4 V | AC/DC 24 V | AC/DC 26,4 V |
Residual ripple
|
2,4 Vss
|
||
Rated consumption DC
|
- | 1,3 W | 1,6 W |
Rated consumption AC
|
- | 1,8 W/3,2 VA | 2,2 W/3,9 VA |
Rated frequency AC
|
50 Hz | 60Hz | |
Input inrush current (A1)
|
- | - | 1,7 A |
Rated short-circuit current
|
- | 1400 mA | - |
Response time / recovery time
|
2 s/3 s | ||
Fuse for control circuit supply
|
resistor PTC
|
||
Electrical isolation supply circuit – control circuit
|
no
|
||
Devices with rated voltage AC 115-120 V / AC 230 V
|
|||
Operating voltage range Un= AC 115-120 V
|
AC 93,5 V | AC 115-120 V | AC 132 V |
Operating voltage range Un= AC 230 V
|
AC 195 V | AC 230 V | AC 253 V |
Rated consumption
|
- | 2,0 W/2,3 VA | 2,4 W/2,8 VA |
Rated frequency AC
|
50 Hz | 60Hz | |
Wire length to the safe transducer
|
(wires installed in parallel; see the notes on the wire lengths)
|
||
Fuse for control circuit supply
|
Short-circuit proof transformer
|
||
Electrical isolation supply circuit – control circuit
|
yes
|
||
Control circuit
|
|||
Conductor resistance in Y1-Y2 or Y1-Y3 (at U
N
dep. on supply voltage)
|
- | - | 70 Ω |
Rated output voltage to the supply of input Y2
|
DC 24 V | - | |
Open circuit voltage
|
- | - | DC 40 V |
Rated current / peak current (inputs Y2, Y3)
|
- | 90 mA/1500 mA | |
Release time tR (K1, K2)
|
- | 60 ms | 80 ms |
Response time tA1 (devices with rated current AC 115-120 V / AC 230 V)
|
- | 180 ms | 300 ms |
Response time tA1 (devices with rated voltage AC / DC 24 V)
|
- | 40 ms | 60 ms |
Response time tA2
|
40 ms | 60 ms | |
Minimum ON time tM1(Y2)
|
tA1 | - | - |
Minimum ON time tM2(Y3)
|
tA2 | - | |
Recovery time tW
|
- | - | 200 ms |
Stand-by time tB
|
300 ms | ||
Output circuit
|
|||
Contact assignment
|
3 enabling current paths with positively driven contacts (NO), 1 signaling current path (NC)
|
||
Rated switching voltage U
UN |
AC/DC 230 V
|
||
Max. continuous current IN per current path, NO / NC
|
8 A/5 A
|
||
Max. total current of all current paths for devices with rated voltage AC / DC 24 V
|
12 A
|
||
Max. total current of all current paths
for devices with rated voltage AC 115-120 V / AC 230 V
|
8A
|
||
Application category according to EN 60947-5-1 360 h-1
3600 h-1 |
AC-15: Ue 230 V, Ie 4 A / DC-13: Ue 24 V, Ie 4 A
AC-15: Ue 230 V, Ie 3 A / DC-13: Ue 24 V, Ie 2,5 A |
||
Short-circuit protection max. fuse
|
6 A class gG or circuit breaker with trigger characteristic B or C
|
||
Short-circuit protection, fuse
|
max 8A
|
||
Mechanical life
|
10x106 switching operations
|
||
General data
|
|||
Creepage distances and clearances between the circuits
|
according to EN 60664-1
depending on device version; see “Electrical isolation, supply circuit”
|
||
Overvoltage category
|
III
|
||
Rated impulse voltage
|
4 kV
|
||
Rated voltage
|
AC 300 V
|
||
Test AC voltage
|
2 kV
|
||
Degree of pollution of the device: inside / outside
|
2/3
|
||
Protection degree according to DIN EN 60529 (housing / terminals)
|
|||
Ambient temperature / storage temperature
|
-25 - +55 °C/-25 - +75 °C
|
||
Dimension diagram
|
K 4-1 (screw terminals / K 4-2 (pluggable terminals)
|
||
Wire ranges fine-stranded / solid or fine-stranded with ferrules
|
2x0,14 - 0,75 mm2/1x0,14 - 2,5 mm2
1x0,25 - 2,5 mm2/2x0,25 - 0,5 mm2 |
||
Permissible torque
|
0,5 - 0,6 Nm
|
||
Weight for devices with rated voltage AC / DC 24 V
|
0,20 kg
|
||
Weight for devices with rated voltage AC 115-120 V / AC 230 V
|
Send an inquiry
Are you interested in this product? Do you need additional information or individual pricing?
Contact us
• For immediate interruption of the power supply – stop category 0
• Monitoring of emergency stop applications
• Monitoring of safety gates
• Protective measures in sections of the safety system
The device has two reset inputs Y2 (without reset monitoring) or Y3 (with reset monitoring). The relays K1 and K2 are actuated either after the reset button (on Y1-Y3) has been pressed or automatically (bridge Y1-Y2). They become self-locking through their own contacts, if there is an electrical connection between terminal A1 and the
supply voltage (emergency stop button, position switches). After this switch-on phase the enabling current paths are closed and the signaling current path is open. If the electrical connections between terminal A1 and the supply voltage are interrupted, the enabling current paths open and the signaling current path closes. The energized state (self-locking) of the two channels is indicated by a green LED K1, K2. The second green LED indicates that supply voltage has been applied. The set-up of an emergency stop facility after stop category 0 (EN 60204-1) is possible. The device corresponds to category 4 for safety-related parts of controls (EN 954-1).
Proper use
The device is available for monitoring transducers (such as emergency stop buttons or
position switches) that are components of protective equipment on machines and are
used for the purpose of protecting people, material and machines.
• The safety category according to EN 954-1 depends on the external circuitry, the
choice of control devices and their placement on the machine.
• Expansion devices or external contactors with positively driven contacts can be used
to multiply the enabling current paths.
• The device and the contacts must be protected at max. 8 A.
• The emergency stop circuit must be closed before the reset button is activated.
• For connecting magnetic switches with reed contacts or sensors with
semiconductor outputs the peak input current must be considered (see “Technical
data”).
• The devices must be installed in a control cabinet with a protection degree of at
least IP 54.
• With AC supply and single-channel circuitry the maximum cable length for the safety
circuit of the transducers must be considered (see the notes on cable lengths and
“Technical data”
Please also note the information provided by your trade association
Cable data section 1,5 mm2
capacity 150 nF/km
resistance 28 Ω/km
temperature +25 °C
Circuit Alternating current (AC) cable not laid out in parallel,max. length lr:1 km
Tap line max. length of tap line l s and max. line capacity C L depending on supply voltage U
UB 115 230 V
CL 37,5 nF 7,5 nF
lS 250m 50 m
Overview of devices / Part numbers | ||||
---|---|---|---|---|
type | Nominal voltage | Terminals | numer sztk/opak. | |
SNO 4003K | AC/DC 24 V | 50 - 60 Hz | Terminal block, rising cage termination | R1.188.0400.1 1 |
AC 115 - 120 V | 50 - 60 Hz | Terminal block, rising cage termination | R1.188.0880.1 1 | |
AC 230 V | 50 - 60 Hz | Terminal block, rising cage termination | R1.188.0890.1 1 | |
SNO 4003K-A | AC/DC 24 V | 50 - 60 Hz | Terminal block, rising cage termination | R1.188.0500.1 1 |
AC 115 - 120 V | 50 - 60 Hz | Terminal block, rising cage termination | R1.188.0900.1 1 | |
AC 230 V | 50 - 60 Hz | Terminal block, rising cage termination | R1.188.0910.1 1 |
Technical data | SNO 4003K | ||
---|---|---|---|
Function
according to EN 60204-1
|
Emergency stop relay
|
||
Function display
|
2 LEDs green
|
||
Function diagram
|
FD 221-3-1 W, FD 221-3-2 W
|
||
Power supply circuit
|
|||
Devices with rated voltage AC / DC 24 V
|
min | typ | max |
Operating voltage range
|
AC/DC 20,4 V | AC/DC 24 V | AC/DC 26,4 V |
Residual ripple
|
2,4 Vss
|
||
Rated consumption DC
|
- | 1,3 W | 1,6 W |
Rated consumption AC
|
- | 1,8 W/3,2 VA | 2,2 W/3,9 VA |
Rated frequency AC
|
50 Hz | 60Hz | |
Input inrush current (A1)
|
- | - | 1,7 A |
Rated short-circuit current
|
- | 1400 mA | - |
Response time / recovery time
|
2 s/3 s | ||
Fuse for control circuit supply
|
resistor PTC
|
||
Electrical isolation supply circuit – control circuit
|
no
|
||
Devices with rated voltage AC 115-120 V / AC 230 V
|
|||
Operating voltage range Un= AC 115-120 V
|
AC 93,5 V | AC 115-120 V | AC 132 V |
Operating voltage range Un= AC 230 V
|
AC 195 V | AC 230 V | AC 253 V |
Rated consumption
|
- | 2,0 W/2,3 VA | 2,4 W/2,8 VA |
Rated frequency AC
|
50 Hz | 60Hz | |
Wire length to the safe transducer
|
(wires installed in parallel; see the notes on the wire lengths)
|
||
Fuse for control circuit supply
|
Short-circuit proof transformer
|
||
Electrical isolation supply circuit – control circuit
|
yes
|
||
Control circuit
|
|||
Conductor resistance in Y1-Y2 or Y1-Y3 (at U
N
dep. on supply voltage)
|
- | - | 70 Ω |
Rated output voltage to the supply of input Y2
|
DC 24 V | - | |
Open circuit voltage
|
- | - | DC 40 V |
Rated current / peak current (inputs Y2, Y3)
|
- | 90 mA/1500 mA | |
Release time tR (K1, K2)
|
- | 60 ms | 80 ms |
Response time tA1 (devices with rated current AC 115-120 V / AC 230 V)
|
- | 180 ms | 300 ms |
Response time tA1 (devices with rated voltage AC / DC 24 V)
|
- | 40 ms | 60 ms |
Response time tA2
|
40 ms | 60 ms | |
Minimum ON time tM1(Y2)
|
tA1 | - | - |
Minimum ON time tM2(Y3)
|
tA2 | - | |
Recovery time tW
|
- | - | 200 ms |
Stand-by time tB
|
300 ms | ||
Output circuit
|
|||
Contact assignment
|
3 enabling current paths with positively driven contacts (NO), 1 signaling current path (NC)
|
||
Rated switching voltage U
UN |
AC/DC 230 V
|
||
Max. continuous current IN per current path, NO / NC
|
8 A/5 A
|
||
Max. total current of all current paths for devices with rated voltage AC / DC 24 V
|
12 A
|
||
Max. total current of all current paths
for devices with rated voltage AC 115-120 V / AC 230 V
|
8A
|
||
Application category according to EN 60947-5-1 360 h-1
3600 h-1 |
AC-15: Ue 230 V, Ie 4 A / DC-13: Ue 24 V, Ie 4 A
AC-15: Ue 230 V, Ie 3 A / DC-13: Ue 24 V, Ie 2,5 A |
||
Short-circuit protection max. fuse
|
6 A class gG or circuit breaker with trigger characteristic B or C
|
||
Short-circuit protection, fuse
|
max 8A
|
||
Mechanical life
|
10x106 switching operations
|
||
General data
|
|||
Creepage distances and clearances between the circuits
|
according to EN 60664-1
depending on device version; see “Electrical isolation, supply circuit”
|
||
Overvoltage category
|
III
|
||
Rated impulse voltage
|
4 kV
|
||
Rated voltage
|
AC 300 V
|
||
Test AC voltage
|
2 kV
|
||
Degree of pollution of the device: inside / outside
|
2/3
|
||
Protection degree according to DIN EN 60529 (housing / terminals)
|
|||
Ambient temperature / storage temperature
|
-25 - +55 °C/-25 - +75 °C
|
||
Dimension diagram
|
K 4-1 (screw terminals / K 4-2 (pluggable terminals)
|
||
Wire ranges fine-stranded / solid or fine-stranded with ferrules
|
2x0,14 - 0,75 mm2/1x0,14 - 2,5 mm2
1x0,25 - 2,5 mm2/2x0,25 - 0,5 mm2 |
||
Permissible torque
|
0,5 - 0,6 Nm
|
||
Weight for devices with rated voltage AC / DC 24 V
|
0,20 kg
|
||
Weight for devices with rated voltage AC 115-120 V / AC 230 V
|